There are several ways to lockout the keypad for an H100+iS7, or S100 (LCD Keypad) drive.

 

Programming


Refer to the settings below depending on which level of lockout is desired:

Level 1

This removes the entire Parameter group from view – only able to view and change CNF and User Group (if applicable).

  • Set the password in CNF-51
  • Enter the password in CNF-50

Level 2

This allows the user to view the Parameter, CNF and User groups but not change anything.

  • Set the password in CNF-52
  • Enter the password in CNF-53

Level 3

This removes the Parameter Group but can view only the CNF and User Groups (without changing).

  • Set the password in CNF-51
  • Enter the password in CNF-50
  • Set the password in CNF-52
  • Enter the password in CNF-53

A highlighted parameter has a boxed outline if there is a password set preventing it from being changed.