How to Reset LS Electric VFDs
If you’re looking to reset a Variable Frequency Drive (VFD) to its factory default
How to Reset LS Electric VFDs
- Access the Parameter Menu:
- For M100 drives, set CF.93 = 1.
- For G100 and S100 drives, set dr.93 = 1.
- For iS7, H100/H100+, and S100 models with an LCD keypad, set CNF40 = 1.
- Confirm Reset:
- The VFD will automatically revert to default settings.
- If you use H100/H100+, ensure CNF43 is set to “Basic” if needed.
- Verify Settings:
- After resetting, check key parameters to ensure proper configuration.
Note: After setting CF.93 ,dr.93, or CNF40, the parameter will always reset back to “0” or “None”. This is normal.